TotalAlert Infinity™ NFPA Medical Gas Notification System



                                                                 2.3.5 B60 Gas Input Board
             NOTE:
             All wiring shall be protected from physical damage  An Area alarm has 8 Gas Inputs. Signals are
             by raceways or conduit in accordance with NFPA 70,
             National Electric Code.                             numbered D01 thru D08. There is a single
                                                                 relay output for general gas fault notification.
            Alarm panels require 100 to 250 VAC                  1.  Identify each pair of twisted gas sensor
            50/60 Hz 250mA power. NFPA Area Wiring                  wires inside the alarm rough-in box (Fig-
            Diagram (Section 3.2)                                   ure 24).

            For NFPA 99 compliance, alarm panel must             2.  Route each pair of sensor wires as shown
            be connected to life safety branch of the               (Figure 25) to appropriate terminals.
            emergency electrical system.                         3.  Connect each pair of sensor wires to
            1.  Remove four screws from plastic power               terminal blocks noting the correct polar-
               supply shield.                                       ity Red(+), Black (-).  NFPA Area Wiring
                                                                    Diagram (Section 3.2)
            2.  Remove plastic shield from power supply.
            3.  Connect incoming line and neutral wires          NOTE:
               to the terminal block. Ground wire con-           If gas sensor wires are landed on the terminal blocks
               nects directly to the rough-in box (chassis)      in the same order as defined by the model number
               at the green screw below the power sup-           of the alarm panel, then initial setup will be easier
               ply (Figure 23).                                  and gas sensor channels will not need to be recon-
                                                                 figured.”  Example T3-A10-OAV means “O” Oxygen
            4.  DO NOT remove or alter the Green factory         is defaulted to D01, “A” Medical Air is defaulted to
               installed ground wire from the terminal           D02, etc. See section 1.6.
               block to chassis.
                                                                                Holes provided for
            5.  Reinstall plastic power supply shield while                     entrance of remote
               making sure all high voltage wires are con-                      wiring
               tained within plastic shield.

            6.  Secure plastic shield with four screws.





          Line Voltage
          Neutral
          Ground




                      Figure 23:  Supply Power Wiring


                  WARNING:


                   RISK OF ELECTRICK SHOCK

             Disconnect power at the circuit breaker                 Figure 24: Remote Sensor Wire Routing
             before removing power supply shield.

                                                             2-5                                4107 9016 58.02