TotalAlert Infinity™ NFPA Medical Gas Notification System




             NOTE:                                              2.3.8 B50 4-20mA Combination
             Each pair of terminals labeled on the signal       Board
             board connector is labeled “+” and “-”. Ensure
             that when a source equipment dry contact is        A Combination alarm can contain a B50
             wired to two master panels, the same side of       board that contains four 4-20mA inputs that
             the dry contact is connected to the same termi-    can be used with a 2 or 3 wire transmitter.
             nal at both panels.  For example, if the source    The board also contains seven signal inputs,
             equipment’s normally closed contact is wired to    which monitor normally closed signal inputs,
             the “+” of the first master panel, ensure it is also   and six normally closed dry contact relay out-
             connected to the “+” terminal of the second        puts. Each alarm panel can have a maximum
             master panel.                                      of one B50 board.
            2.3.7 B4X Relay Output Board
                                                                Identify each set of field installed 4-20mA

            A Master or Combination alarm can contain           input signal wires (2 or 3 wires per set) inside
            multiple relay output boards; up to a maxi-         the alarm rough-in box. Route each set of in-
            mum of 4 boards with 16 relay outputs each.         put wires to the appropriate terminals on the
            The B4X boards (B40, B41, B42, B43) utilize         B50 board. Connect each set of signal wires
            normally closed dry contact relay outputs.          to the terminal blocks, noting the correct
            The outputs on the B4X boards are labeled           polarity (Figure 28).
            Y01 through Y16.

            Identify each pair of field installed relay
            output signal wires inside the alarm rough-in
            box. Route each pair of relay output wires as
            shown in Figure 27 to the appropriate termi-
            nals on the relay board. Connect each pair
            of signal wires to the terminal blocks, noting
            the correct polarity (+,-). Refer to NFPA Mas-
            ter/Combination Wiring Diagram (Section
            3.1/3.3).












                                                                       Figure 28:  B50 Board Wire Routing














                  Figure 27:  B4X Board Wire Routing

                                                             2-7                                4107 9016 58.02