Page 459 - Womens Pavilion
P. 459

TotalAlert Infinity™ NFPA Medical Gas Notification System



           2.3.9 Alarm Panel “Mirroring”                       2.3.11 Ethernet

                                                               Alarms can be connected to a facility’s net-
           Each alarm panel has an Ethernet port on the        work via Ethernet by plugging the network
           back of the front panel assembly.  By con-          cable to the port provided on the back of the
           necting the alarm to the hospital network,
           via Ethernet, or directly cabling it to another     alarm front panel.
           alarm panel, signals and gas pressures can
           be pulled from one panel and displayed on
           another panel.

           A category 5 CROSS OVER cable is required
           for connecting alarm panels directly to each
           other. Otherwise, standard cabling can be
           used with a facility’s Ethernet hub or switch
           to connect panels.
           2.3.10 General Fault Relay


           The B60 Gas Input board is supplied with an
           alarm panel general fault output relay.
           This relay has a set of dry contacts that is
           wired normally closed.                                Ethernet
           The relay will activate when ANY alarm on         Connection
           the ENTIRE alarm panel is activated. Relay
           will remain activated as long as alarm condi-                Figure 29:  Ehernet Connection
           tion is active, even if audible alarm is silenced
           by MUTE button.
           When alarm condition is corrected, relay will
           deactivate. Relay contact ratings are 5A @
           30VDC / 3A @ 250VAC. Refer to NFPA Area
           Wiring Diagram (Section 3.2).




























           4107 9016 58.02                                  2-8
   454   455   456   457   458   459   460   461   462   463   464