Page 464 - Womens Pavilion
P. 464

TotalAlert Infinity™ NFPA Medical Gas Notification System



            3.0  Wiring Schematics


            3.1  NFPA Master Wiring Diagram




                                                                                               MAIN DISCONNECT PROVIDED BY OTHERS FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM FIELD SIGNAL WIRING TO BE MINIMUM 22AWG  MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD  TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM  -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX. INPUTS FROM DRY NORMALLY-CLOSED CONTACTS FROM SOURCE  EQUIPMENT OR LINE PRESSURE SWITCHES. R













                                                                                             Notes: Figure 35: Wiring Diagram for TotalAlert Infinity™ Master Alarm  1.   2.   3.   RESISTANCE  4.   5.   6.   7.   8.   ONLY.











































                                                                                   FACTORY WIRED   CHASSIS GROUND







                                                                                   ENCLOSURE   GROUND SCREW



                                                             3-1                                4107 9016 58.02