TotalAlert Infinity™ NFPA Medical Gas Notification System
3.0 Wiring Schematics
3.1 NFPA Master Wiring Diagram
MAIN DISCONNECT PROVIDED BY OTHERS FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM FIELD SIGNAL WIRING TO BE MINIMUM 22AWG MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX. INPUTS FROM DRY NORMALLY-CLOSED CONTACTS FROM SOURCE EQUIPMENT OR LINE PRESSURE SWITCHES. R
Notes: Figure 35: Wiring Diagram for TotalAlert Infinity™ Master Alarm 1. 2. 3. RESISTANCE 4. 5. 6. 7. 8. ONLY.
FACTORY WIRED CHASSIS GROUND
ENCLOSURE GROUND SCREW
3-1 4107 9016 58.02