TotalAlert Infinity™ NFPA Medical Gas Notification System
2.4.2 Locally Installed Sensors 2.4.3 Remotely Installed Sensors in
Pipeline
1. Remove sensor module from shipping
carton. 1. Remove sensor from shipping carton.
2. Connect sensor with DISS fitting to the
appropriate DISS check at the top of the 2. Connect sensor with DISS fitting to the
appropriate DISS Check on the hospital
rough-in box. Verify Gas ID labels match
between the sensor and piping to ensure pipeline or BeaconMedæs Zone Valve box.
Verify Gas ID labels match between the
no cross connections occur. Repeat this sensor and piping to ensure no cross con-
process for all sensors within alarm panel.
3. Connect wires into input terminals of B60 nections occur.
board (see section 2.3.5). 3. Wire nut pigtail to field installed wiring.
Note polarity of wiring and corresponding
field wiring color or number for later (see
section 2.3.5).
NOTE:
Do not ground shield drain wire at sensor.
Figure 33: Local Sensor Mounting
NOTE:
Figure 34: Remote Sensor Module Connection
If gas sensor wires are landed on the terminal
blocks in the same order as defined by the
model number of the alarm panel, then initial
setup will be easier and gas sensor channels
will not need to be reconfigured.” Example
T3-A10-OAV means “O” Oxygen is defaulted to
D01, “A” Medical Air is defaulted to D02, etc.
See Section 1.6.
2-11 4107 9016 58.02