TotalAlert Infinity™ NFPA Medical Gas Notification System




            3.3  NFPA Combination Wiring Diagram









                                                                                            MAIN DISCONNECT PROVIDED BY OTHERS FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM FIELD SIGNAL WIRING TO BE MINIMUM 22AWG  MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD  TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM RESIS- -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX. SIGNAL INPUTS (UP TO 8) FROM GAS SENSOR MODULES. SIGNAL INPUTS FROM DRY NORMALLY-CLOSED C













                                                                                          Notes:  1.   2.   3.   TANCE  4.   5.   6.   7.   8.   USING TABLE 1.  9.   10.









































                                                                                         FACTORY WIRED   CHASSIS GROUND Figure 37: Wiring Diagram for TotalAlert Infinity™ Combination Alarm







                                                                                         ENCLOSURE   GROUND SCREW



                                                             3-3                                4107 9016 58.02