Page 246 - Saber® Installation & Startup
P. 246

INSTALLATION & STARTUP

            Chapter 22 Initial Startup Procedure



            Startup Procedure

               SCC and Other Components
               1)  Confirm that the power to the SCC is off. Turn ON all breakers in SCC, set all Outputs to AUTO and close the
                   door.



                                                                        Breakers up for ON











                                                                        Switches toward middle of
                                                                        Output Board for AUTO



                             AUTO
                     Swiched to the Inside

                          Manual ON
                    Swiched to the Outside
                                                                             OFF
                                                                             Swiched to the Middle of the output
                                                                              Board

               2)  Confirm that all doors are closed and turn on the power to each electrical panel at
                   load center.
               3)  Pull out e-stop on HMI panel. (E-1063 as well as any in-bay e-stops).
               4)  Flush air line for 1 minute and connect to system air regulator. Set air pressure to
                   105 psi and check HMI for E-Stop condition. Troubleshoot E-Stop circuit if necessary.
               5)  Check the Fault Screen on the HMI for any faults and troubleshoot if needed.
                                                                                     System Pneumatic
               6)  Turn down air pressure while someone watches the HMI (Monitor Inputs field) for   Regulator Assembly
                   LOW AIR Input to turn off. The LOW AIR Input should turn off at 75 psi and lower.
                   Adjust the pressure switch on the System Pneumatic Regulator Assembly to achieve this condition.
               7)  Reset air pressure to 105 psi.
               8)  Turn off disconnect at each electrical panel and verify e-stop trips. (MCC, Dryer, and any other e-stops).
               9)  Perform startup on procedure on all optional equipment if not already done. (Dryer, RO, etc.)













             22-6   Belanger, Inc. * PO BOX 5470 * Northville, MI 48167-5470 * Ph (248) 349-7010 * Fax (248) 380-9681    1MANUL290
   241   242   243   244   245   246   247   248   249   250   251