HEATING AND AIR CONDITIONING - REFRIGERANT                        41-27

                        Symptom              Possible Cause            Diagnostics                Action

                                                                                          •Check the expansion
                                                                                            valve.

                                          •System leakage - check                         •Blow off the dirt inside
                  Vaccum at the low end     connector and exposed                           the  expansion  valve
                  and low pressure at the   parts.                                          with compressed air.
                  high end. Frost or dew   •The flow of the refrigerant  System leakage -   •Replace the condenser.
                  on the pipes before and   is blocked by steam or  insufficient refrigerant,   • Vacuum the system
                                                                                            and Add some
                  after the                 dirt.                 unable to circulate.      refrigerant.
                  condensing/drying can   •The flow of the refrigerant                    • If any leakage in the
                  or expansion valve.       is intervened by leakage                        expansion valve,
                                            in the expansion valve.
                                                                                            replace it.
                                                                                          • Check for leaking
                                                                                            points.

                 • Unsmooth circulation of refrigerant (condition: ineffective cooling system)













                                                                                                                    41










                        Symptom              Possible Cause            Diagnostics                Action

                  Low  pressure  at  both   Refrigerant blocked by                        •Replaced the damaged
                  high and low ends. Frost   dirt                 System blocked           parts
                  on the condenser pipe.                                                  •Replace the condenser