HEATING AND AIR CONDITIONING - REFRIGERANT 41-33
2. Vacuum
(a). Connect the connectors of the A/C
refrigerate collecting/filling system to the
high and low ends of the A/C system
respectively.
fuwx41061
(b). Turn on the high pressure and low pressure
valves of the A/C refrigerate collecting/
filling system.
(c). Select the "Vacuum" operation of the A/C
refrigerate collecting/filling system and set
the timer to 15 minutes.
(d). Start the vacuuming process of the A/C
refrigerate collecting/filling system. When
the set timer is reached,the system will
stop working. 41
(e). Turn off the high pressure and low
pressure valves at the connectors of the A/
C refrigerate collecting/filling system and
fuwx41062
record the reading of the pressure gauge.
(f). Maintain the pressure for 15 minutes. If the reading remains unchanged, it means
there is no leakage in the A/C pipe. Top up the refrigerant, lubricant and coolant. If
the reading grows, check for leakage in the A/C system.
(g). Disconnect the connectors of the A/C refrigerate collecting/filling system to the high
and low ends of the A/C system respectively.