Root Cause

            Due  to  mechanical  failure  of  compressor  packing  seal,  excessive  H2  released  from  packing  vent  line.

            Sudden release of H2 gas from packing vent lines comes into contact with hot surface of reactor (303R202)
            outlet line.


             Recommendations

            1.  Compressor packing vent lines of both compressors need to be rerouted and further extended upward.

            2.  Compressor 303K201A packing leak to be attended.




             Case 22                              Date: 11.07.2019                      Time: 18:30 hrs.



             Incident

            An employee fumbled near monkey ladder in Parex unit battery limit of PX-2 during the finishing column bottoms
            ine up towards tank T-03. It resulted in minor inflammation in soft tissues of his right knee and upper parts of

            abdomen. After giving first aid treatment he returned back to work.


































             Root Cause

            Unsafe practice by jumping over the space provided for monkey ladder.



             Recommendations

            1.  Caution board to be provided.
            2.  Fluorescent marking to be done to distinguish monkey ladder gap and platform.
            3.  Toe guard to be provided.