Root Cause

            EOT movement limit restriction towards Extreme West side of plat former Compressor.



             Recommendations

            1.  For roller assembly metallurgy & strength related issues OEM to be consulted
            2.  JSA to be done in view of EOT travel restriction and space constraint and Barrel shifting, sling adjustment
            related points to be incorporated in JSA with all potential possible hazards.




             Case 25                              Date: 15.05.2019                       Time: 08:00 hrs.


             Incident

            A  casual  of  inspection  department  opened  the  main  door  of  the  inspection  building  and  found  that  the
            entrance area was smoky. Immediately Fire & Safety team reached the site and found that towards just right

            to  the  entrance  of  inspection  building,  electrical  wirings  are  hanging,  sofa  found  totally  burnt,  One  wall
            mounted fan found burnt, tube light found burnt and one TV ahead to lobby is found burnt. Most of the walls
            and roof towards right inside lobby found blackish with smoke.









                                  Location of wall mounted fan             Burnt tube light











                                                Burnt electrical board





                          Location of L Shape Sofa




             Root Cause


            Jamming of wall mounted fan shaft resulted in generation of heat and melting of plastic components and
            subsequently caused fire. The thermostat present near the fan motor portion did not act and hence, the
            power supply was not cut off.