Recommendations
1. Periodic maintenance of wall mounted fan shall be implemented.
2. As far as possible, wall mounted fans with plastic body are to be removed wherever AC is provided. If
there is no Air conditioning, then ceiling fan is to be provided in place of wall fan. If there is space
constraint, then industrial type wall fans may be considered for such locations.
3. Users to be sensitized at regular intervals about switching off the power in their respective area for
lighting, fan, computer, AC, etc, when not required.
4. Along with night security audit of plant, the non-plant building may be checked for switched off
condition of power supply during odds hours.
5. Smoke detectors to be installed in the building. Where it is not available as on date.
Case 26 Date: 02.05.2020 Time: 14:38 hrs.
Incident
While replacing the downstream passing valve of Controller (PC-0409), Hydrogen leakage withsubsequent
fire observed from the upside flange of the valve. Fire was extinguished by using DCP Fire extinguishers.
Root Cause
Passing of bypass valve of Controller and Inadequate Nitrogen purging.
43