Case 31 Date: 08.07.2020 Time: 15:30 hrs.
Incident
Furnace oil (FO) was leaking from pin hole developed in 10”line in pipe sleeper along Road-C. FO line was
depressurized & foam blanketing was applied by F&S on the pool of HC. Pin hole in the line was clamped
after line depressurization. Spilled HC was lifted through super sucker and unsafe condition was averted.
Leak from 10 inch line
Root Cause
Pin hole leak from 6 O' clock position due to material defect.
Recommendations
1. Sleeve welding of leaky portion.
2. Oil to be removed from the nearby area.
3. Water logging around the sleeper pipe area to be cleared.
Case 32 Date: 21.09.2020 Time: 16:20 hrs.
Incident
A minor fire was noticed at east side of TS-1 second floor in the fumes of oil coming out from insulation
of vacuum slop draw line. Immediately vacuum slop draw was stopped and fire was extinguished by
operating remote operated HVLRM.
Trend - Vacuum column
pressure increase during
back-flushing due to
reduction in CW flow