Reference Guide                                                         Fire Strategy



                          B1 – Means of Warning and Escape


                   1.5.1 Fire alarm and detection system


               All stores are to be provided with an automatic fire alarm and detection system to not less

               than Category L3 standard, in accordance with BS5839-1. It is noted that this is an
               enhancement above the required category M alarm system.

                   1.5.2 Occupancy Numbers


               Anticipated population numbers for the model store design have been developed based on a

               floor space factor of 4.0m2 for a shop sales area. This value accords with information
               provided by Co-op and takes account of the recommendations of ADB Table C1, Note 1 and

               is in accordance with BS9999:2017 Table 9.
                           Floor Area (m2)       Floor Space Factor (m2/person)   Anticipated Population Number
                               280                          4                           70


               It is anticipated that up to 5 staff members may be present at all material times, though may
               be situated either front-of-house or back-of-house. This results in a total building population
               of 75 persons.




                   1.5.3 Fire Exits


               Where the anticipated population of a building, or part thereof, is >60 persons, ADB requires
               that an alternative escape route is provided. Where two distinct exits are provided, it is

               reasonable to assume that one of these may become unusable in the event of a fire, and it
               follows that each individual exit should have sufficient capacity to accommodate the
               population of the entire floorplate.


               The following table outlines the exit capacity of exits from a given width:

                                    Maximum number of persons      Minimum width (mm)
                                              60                         750
                                             110                         850
                                             220                        1,050
                                         More than 220              5mm per person


               Note: the above requirements do not take account any further limitations stipulated in Approved Document M:
               Access to and Use of Buildings.





              Document Classification     Final    Document Ref:   3.1-RCS-RHSE-(110)-262   Version   1.1
                                                                                                               6