Page 124 - RotF - Electrical Specification_Neat
P. 124

PARTICULAR ELECTRICAL SPECIFICATION
                                 Version 2014-2


                      Where existing lighting bus-bars are going to be obscured and rendered inaccessible by the
                      installation of sections of new plaster ceilings then this bus-bar must be repositioned to
                      those areas where it will be accessible above false ceiling tiles.

                      All connections i.e. plug-in ceiling roses, rendar units, bus-bar tap-off units must be readily
                      accessible in ceiling voids to allow the safe isolation of the new lighting equipment. Where
                      there are large areas of plaster ceilings features installed then flush ceiling access panels
                      must be fitted to enable access to the lighting connection points .

                      When installing new circuits the contractor shall identify these at the respective distribution
                      boards.

               1.4.2.2  Lighting

                      The Contractor is note the scope requirements for the replacement of light fittings, where
                      existing fittings are to be retained the Electrical Contractor will  take down the existing
                      fittings and clean them before re-installation.

               1.4.2.3  Emergency Lighting

                      The contractor shall check that the exiting circuit arrangements comply with BS 5266 and are
                      suitable for re-use.

                      It is imperative that the new emergency lighting system will not only operate under mains
                      failure conditions but also on phase failure and local circuit failure.


                      Where the existing wiring systems etc. to do not meet with the above requirements then the
                      contractor shall install appropriate circuits, test relays etc. to satisfy the above requirements.

                      A timed test facility is employed in most Restaurants to enable routine testing of the
                      emergency lighting installation.


                      The contractor will check that the test facility is functioning correctly and where it is not
                      operating correctly make appropriate adjustments to satisfy himself that the test discharge
                      periods meet with BS 5266.

                      Sufficient luminaires and emergency exit signs must be installed in compliance with BS 5266.

               1.4.2.4  Fire Alarm Systems

                      The contractor  will establish that the existing fire alarm system in the areas to be
                      refurbished meets with BS 5839.

                      The Contractor will determine that the removal of a single device registers as a fault at the
                      panel without preventing the correct operation of the remaining devices on the same wiring
                      zone. Any system that fails this test must be recommended for replacement.




                                                McDonalds Restaurants Ltd
                                                           7
   119   120   121   122   123   124   125   126   127   128   129