                   2.24  No LEDs or Displays are Lit on the Area Alarm
                   Chapter 2: Troubleshooting Procedures

                   2.24 No LEDs or Displays are Lit on the Area Alarm



                                 SHOCK HAZARD:
                                 The potential for electric shock exists with electrical equipment. Use
                                 caution when troubleshooting any electrical device.

                                 1. The building supply breaker is in the ON position.
                                     Yes   No
                                      ↓     → Turn the building supply breaker to the ON position. If this
                                                solves the problem, go to “Final Actions” on page 2-7.
                                                Otherwise, go to step 2.


                                 2. The Area Alarm’s power supply switch to the ON position.
                                     Yes   No
                                      ↓     → Turn the power supply switch to the ON position (see “Area
                                                Alarm Power-Up” on page 1-112). If this solves the problem, go
                                                to “Final Actions” on page 2-7. Otherwise, go to step 3.

                                 3. The power supply’s fuse is intact.
                                     Yes   No
                                      ↓     → Replace the power supply’s fuse (refer to procedure 4.15 on page
                                                4-40). If this solves the problem, go to “Final Actions” on page
                                                2-7. Otherwise, go to step 4.

                                 4. The two orange leads coming from the power supply to the breakout board
                                     are connected.

                                     Yes   No
                                      ↓     → Connect the two orange leads from the power supply to the
                                                breakout board (refer to procedure 4.7 on page 4-22). If this
                                                solves the problem, go to “Final Actions” on page 2-7.
                                                Otherwise, go to step 5.

                                 5. The facility’s supply voltage is connected to the alarm’s terminal block.
                                     Yes   No
                                      ↓     → Connect the facility’s supply to the alarm’s terminal block. For
                                                the wiring diagram, refer to FO 3-4 at the rear of this document.
                                                If this solves the problem, go to “Final Actions” on page 2-7.
                                                Otherwise, go to step 6.