TotalAlert Infinity™ NFPA Medical Gas Notification System



                                                                 F = Low Alarm Settings Tab
                                                                 You can remove the low alarm set point or
                                                                 customize the low alarm set point.
                                                                 To remove the low alarm set point:

                                                                 1.  Touch the NONE tab.
                                                                 2.  Touch the check on the CONFIRM SET-
                                                                    TINGS CHANGE screen.

                                                                 To customize the low alarm set point:
                                                                 1.  Touch the ADJUST tab.
                                                                 2.  Enter the new set point.
                      Figure 151: Source Location                3.  Touch the Save button.

            E = [Units of Measure] Tab
            To set up the 4-20mA device:
            1.  Touch the tab for “4MA=” to set the low
               measurement point of the device (zero
               for example) and press the save button to
               exit.
            2.  Touch the tab for “20MA=” to set the high
               measurement point of the device (100
               for example) and press the save button to
               exit.
            3.  Touch the tab for “Units=” to set the
               method of measurement (percent for                        Figure 153: Low Alarm Settings
               example), type in the measurement type
               and press the save button to exit.                G = High Alarm Settings Tab
            4.  Touch the X button in the upper right to         You can remove the high alarm set point or
               close the screen.                                 customize the high alarm set point.
                                                                 To remove the high alarm set point:

                                                                 1.  Touch the NONE tab.
                                                                 2.  Touch the check on the CONFIRM SET-
                                                                    TINGS CHANGE screen.

                                                                 To customize the high alarm set point:
                                                                 1.  Touch the ADJUST tab.
                                                                 2.  Enter the new set point.
                                                                 3.  Touch the Save button.





                   Figure 152: Units of Measure Tab







                                                             4-37                               4107 9016 58.02