TotalAlert Infinity™ NFPA Medical Gas Notification System
Active Alarm The B40 (or B41, B42, B43) board must be
To setup active alarm General Message: initialized. Touch Primary Settings from the
1. Touch the General Message tab to activate right side menu, then select “Initialize Mod-
general message. ules”. Press the “Scan” button to make sure
2. Touch the gray text box at bottom of screen the B40 board is set up, as it should turn
to type in general message. green. Once the B40 board is green, press the
3. Using the keyboard, enter the message that “Save” icon to exit the screen. Exit the “Pri-
you would like to be active when in alarm mary Settings” screen.
mode and save.
To setup active alarm Option Message:
1. Touch the Optional Message tab to activate
optional message.
2. Touch the 01 tab.
3. Using the keyboard, enter the optional mes-
sage that you would like to be active when
in alarm mode and save.
Configuring Additional 4-20mA Devices
Configure additional 4-20mA devices by touch- Figure 155: Initialize Modules Screen
ing the number on the numeric display that The next step is to select the “Relay Outputs”
corresponds with the gas badge and repeating from the menu on the Configuration Screen.
the steps listed above. The B40 board should be highlighted in
Green (or other Relay Output board installed
4.7.2 Relay Output Board (B4X in the rough-in box).
Board) Select the signal that corresponds to the
To configure a Relay Output, start on the output wires on the relay board (Y01 for
CONFIGURATION screen. Users are always example).
prompted to enter the password when ac-
cessing this screen.
Type the password, and touch the Enter but-
ton.
The CONFIGURATION screen displays.
Figure 156: Relay Outputs Screen
After selecting the signal, you will need to
assign it to an alarm signal to send. Select
“Wired” on the Relay Output screen if the
signal to be relayed is wired into the rough-in
Figure 154: Configuration Screen box.
4107 9016 58.02 4-38