TotalAlert Infinity™ NFPA Medical Gas Notification System
Select the corresponding “Ethernet” if an Eth-
ernet signal has been set up. (See Mirroring
in Section 4.6.4.
Figure 159: Relay Output One Signal
3. “Many Signals” allows the user to group
multiple signals on a single relay output.
Figure 157: Relay Output Signal If any of the signals goes into alarm condi-
tion, the relay output will report an alarm
There are four choices for the relay output condition. Press “Many Signals” to move
signal. to the Relay Output screen and select
from 1 to 10 signals to group together.
Select the number 01 to start, then select
the first signal to be grouped by pressing
the corresponding number on the Relay
Output (such as X01 from the B10 board).
Press Save to return to the Many Signal Re-
lay Output screen. Next select 02 to cap-
ture the second signal to be monitored.
Repeat up to a grouping of 10 signals.
Figure 158: Relay Output Signals Screen
1. A single “Any Fault” which will report a
general alarm fault if any of the alarm sig-
nals on the alarm go into alarm condition.
To select “Any Fault”, press the blue “Any
Fault” to change it to green with the check
mark. Then press Save to return to Relay
Outputs and set up additional outputs.
2. “One Signal” reports a single signal
through the relay output. When pressing Figure 160: Relay Output Many Signals
“One Signal”, the next step is to assign 4. “Gas Sensor Alarm Fault” allows the user
the signal to be transmitted. On the Relay to report a fault condition based on a gas
Output screen, select the Input Signal to sensor through the relay output. When
be transmitted (X01 from the B10 board choosing Gas Sensor Alarm Fault, select
for example). Press Save to return to the the gas sensor to be monitored from the
Relay Outputs screen. list. Press Save to return to the Relay Out-
puts screen.