TotalAlert Infinity™ NFPA Medical Gas Notification System



            Select the corresponding “Ethernet” if an Eth-
            ernet signal has been set up. (See Mirroring
            in Section 4.6.4.













                                                                      Figure 159: Relay Output One Signal

                                                                 3.  “Many Signals” allows the user to group
                                                                    multiple signals on a single relay output.
                    Figure 157: Relay Output Signal                 If any of the signals goes into alarm condi-
                                                                    tion, the relay output will report an alarm
            There are four choices for the relay output             condition.  Press “Many Signals” to move
            signal.                                                 to the Relay Output screen and select
                                                                    from 1 to 10 signals to group together.
                                                                    Select the number 01 to start, then select
                                                                    the first signal to be grouped by pressing
                                                                    the corresponding number on the Relay
                                                                    Output (such as X01 from the B10 board).
                                                                    Press Save to return to the Many Signal Re-
                                                                    lay Output screen.  Next select 02 to cap-
                                                                    ture the second signal to be monitored.
                                                                    Repeat up to a grouping of 10 signals.



                Figure 158: Relay Output Signals Screen
            1.  A single “Any Fault” which will report a
               general alarm fault if any of the alarm sig-
               nals on the alarm go into alarm condition.
               To select “Any Fault”, press the blue “Any
               Fault” to change it to green with the check
               mark.  Then press Save to return to Relay
               Outputs and set up additional outputs.
            2.  “One Signal” reports a single signal
               through the relay output.  When pressing              Figure 160: Relay Output Many Signals
               “One Signal”, the next step is to assign          4.  “Gas Sensor Alarm Fault” allows the user
               the signal to be transmitted.  On the Relay          to report a fault condition based on a gas
               Output screen, select the Input Signal to            sensor through the relay output.  When
               be transmitted (X01 from the B10 board               choosing Gas Sensor Alarm Fault, select
               for example). Press Save to return to the            the gas sensor to be monitored from the
               Relay Outputs screen.                                list.   Press Save to return to the Relay Out-
                                                                    puts screen.