TotalAlert Infinity™ NFPA Medical Gas Notification System
4.7.4 BACnet Set-Up
The TotalAlert Infinity™ alarms employ the
TCP/IP family of protocols for communica-
tion and each device has a unique IP address.
The alarm utilizes a built-in Ethernet connec-
tion for BACnet transmission of signals to a
Building Automation System. The TotalAlert
Infinity™ alarm panel conforms to the BACnet
protocol and includes a Protocol Implemen-
tation Conformance Statement (PICS). Figure 166: BACnet Screen
• Touch the MISCELLANEOUS tab located • Save the BACnet device name by touching
on the configuration screen. the save button located in the top right
corner of the screen.
Figure 164: Configuration Screen
• Touch the BACNET tab to access the BAC- Figure 167: BACnet Device Name
NET control screen. • To add the ID, touch the DEVICE ID tab
and enter the ID number provided by the
Building Management System administra-
tor.
Figure 165: Miscellaneous Screen
• To allow BACnet communication, touch
the BACnet ON tab.
• To add the name, touch the DEVICE Figure 168: BACnet Device ID
NAME tab and enter the name through • Save settings.
the on screen keyboard. • Touch the X in the top right corner to exit
out of the BACnet setup screen.
4-41 4107 9016 58.02