GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         It is to be the responsibility of the Electrical Contractor to satisfy himself that all switch
                         rooms and ducts and cupboards, etc. shown for the routing/positioning of electrical
                         services and equipment are adequate in size, (bearing in mind future access requirements
                         for maintenance) for the equipment they are intended to house).

                         The Electrical Contractor is to allow taking receipt of the contributor’s information and
                         attending meetings as necessary for the purpose of co-ordination, both in terms of design
                         and installation.

                         The  Electrical Contractor is to be responsible for the accurate establishment of the
                         mounting height and finite location, in relation to the equipment served and the location
                         of other services, of all electrical accessories or equipment forming part of the installation
                         and is to produce detailed, installation drawings where necessary as requested by other
                         members of the design/construct team.

                         The  Electrical Contractor is to include for all works described in addendums issued
                         subsequently, as complementary documents to this specification, during the tender
                         period. Each addendum is to have a reference and the Electrical Contractor is to clearly
                         identify all the addenda received during the tender period and included within the tender
                         figure.
                         The works are to be designed and installed to facilitate inspection, cleaning and repairs

                         and for operation in which safety and continuity of service are to be the first
                         consideration. All apparatus is to be designed to ensure satisfactory operation under the
                         atmospheric conditions prevailing and under such variations of load and voltage as may
                         be met under working conditions on the system, including those due to faulty
                         synchronising within the rating of the apparatus. The apparatus is to also be of an
                         adequate strength to withstand the electro-mechanical forces that may be set up by the
                         prospective short circuit currents.
                         The installation is to incorporate every reasonable precaution and provision for the safety
                         of all those concerned in the operation and maintenance of  the works and associated
                         works supplied by others. The Electrical Contractor is to provide a Risk Assessment of the
                         proposed installation as part of the design procedures.

                         All design work is to be carried out under the direct control of suitably qualified  and
                         experienced personnel.

                         The Electrical Contractor is to produce detailed schedules of all equipment proposed for
                         use within the works for comment by the Project Manager.

                         The Electrical Contractor is to be responsible for all downtaking of redundant electrical
                         services that are not required by the scope of this specification. However, all downtaking
                         is to be agreed with the Project Manager/Client for approval/comment prior to execution.