GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         The  Electrical Contractor  shall supply and install wiring from the HVAC panel to each
                         extract fan.

                         Fixed wiring shall terminate in an isolator mounted adjacent to each fan. Final
                                                                  2
                         connections shall be carried out using 1.5mm  3 core PVC 3183Y flexible cable.
                         The isolator shall be as IP65 rated.
               2.16.6  Overdoor Air Curtain


                         An over door air curtain system will be installed by the HVAC Contractor inclusive of a
                         door fan and remote reverse cycle heat pump.
                         The Electrical Contractor will provide a three-phase supply and isolator for the remote

                         condenser/heat pump plant; this will normally be installed in the roof plant space.
                         The isolator will be IP65 rated, rotary type rated at 25A TP&N with padlock facilities.

                         The supply cable will be multicore XLPE/SWA or YY.

                         The door fan will be  provided with an SP&N electrical supply from the roof plant, the
                         Electrical Contractor will install a 3-core YY cable between the roof plant and the door fan,
                         the supply cable will terminated in a 25A SP&N rotary isolator with pad lock facilities.

               2.16.7  Refrigeration Plant

                         A walk-in freezer and cold room will be installed by a specialist.

                         The Electrical Contractor shall supply and install a sub-main to the refrigeration control
                         panel.
                         All other power and control wiring will be provided by the specialist.

               2.16.8  Gas Fired Domestic Water Heater and Circulating Pump

               2.16.8.1  Heater


                         A floor standing gas fired domestic hot water heater will be supplied and installed by
                         others.
                         The Electrical Contractor shall supply and install a single phase supply terminating in a
                         fused connection unit as MK Electric Ltd K972 ALM.

                         Final connection to the heater shall be carried out by the Electrical Contractor using 3
                                    2
                         core 1.5mm  heat resistant cable 3183 TQ.
               2.16.8.2  Flue Dilution Fan (Where Fitted)

                         When specified a single phase supply shall be terminated within 150mm of the water
                         heater feed to supply the flue dilution fan. The rating will be as identified by the boiler
                         installation Contractor.