GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         Final connection to the terminals within the HVAC and panel shall be carried out by the
                         Electrical Contractor.

                         The  Electrical Contractor  shall fit each cable core with a cable marker as supplied by
                         Partex (or equal and approved) to correspond with the terminal number within the panel.
                         Similar cable markers shall also be fitted at the equipment end of the cable.

               2.15.2  Controls

                         All items of controls i.e. sensors, thermostats etc will be provided by the Mechanical
                         Contractor.

                         All equipment with the exception of wall mounted thermostats and sensors will be fixed
                         by the HVAC contractor.

                         The  Electrical Contractor shall connect all control items and shall fix and connect wall
                         mounted thermostats and sensors.
                         Final connections to control items shall be made as follows:

                         EQUIPMENT                                FINAL CONNECTION DETAILS
                         Wall mounted thermostats and sensors     Belden screened control cables via a flush
                                                                  mounted Besa box
                                                                                2
                         Duct sensors, air pressure  switches,  2 Core 0.5mm  3182TQ flex connected to
                         thermal cut outs                         the fixed  connector block in  a Besa box.
                                                                  Flex to be fitted with a nylon packing gland
                                                                  at both ends.


                         Final connections to controls mounted externally to be made as above but all conduit box
                         lids to be fitted with neoprene gaskets and nylon packing glands to be of the watertight
                         type, complete with a PCP sealing ring.

               2.15.1  Intruder Alarm

                         The Electrical Contractor is to provide an interface between the intruder alarm control
                         panel and the Restaurant lighting control system to enable the complete lighting
                         installation to be switched on when the alarm is triggered.

                         The Contractor is to liaise with the intruder alarm specialist to ensure this interface
                         functions correctly.