GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         For kiosks with a floor connection only, the socket will be located in the nearest service
                         void from which service containment is to be routed to the foot of the kiosk in a floor
                         chase.

               2.14.1.6  Digital Tablet Tables

                         Provide a switched fused connection unit adjacent to the location of the Tablet table as
                         identified on the Architects drawing.

                         The final location of the connection unit will be determined by the containment route to
                         the table, i.e. whether it is connected to the ceiling or floor only.

                         The circuit to the digital tablet table will be fitted with 30mA RCD protection.

                         For tables with a ceiling connection the connection unit will be located in the ceiling void
                         directly above the table.
                         For tables with a floor connection only, the connection unit will be located in the ceiling at
                         the top of the wall chase linking the floor chase to the table.

                         Supply and fit four BS1363 twin switched sockets within the table base enclosure for the
                                                                              2
                         connection of the digital tablet chargers. Connect a 4mm  3-core YY cable between the
                         fused connection unit and the twin sockets in the table.

               2.14.1.7  Kitchen Video System (KVS)

                         Provide switched sockets located in the ceiling void fixed immediately above the location
                         identified on the  McDonalds specialist Contractors  drawing,  where information is not
                         available as indicated by the appendices of this specification, or otherwise as directed by
                         the Project Manager.

               2.14.1.8  Counter

                         Provide the following for the counter positions:

                         Position Type               Service Requirements
                         Order take/ till point/pod   2 x twin switched sockets
                                                     1 x fused connection unit
                         Collection point            2 x twin switched sockets
                         Local data cabinet          2 x twin switched sockets


                         A minimum of two distribution circuits will be provided at the counter so that trading is
                         not interrupted by a single circuit failure; both circuits will be of the same supply phase.
                         Each counter station will be presented with multiple power supply outlets connected
                         interleaved to both circuits.

                         Power supplies will be routed in one of two dado trunkings fitted to the underside of the
                         counter; the second trunking will be used by the data system installer.