GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



               2.14.3  Containment


               2.14.3.1  Data Cabling Generally

                         Provide cable basket linking between the central data cabinet and all final terminal points
                         for the installation of data cabling by the McDonalds specialist Contractor.

                         Basket will light duty with a minimum side wall height of 30mm, the width of basket will
                         vary between 200mm and 50mm, the selected width will be sufficient to allow the
                         installation of all data cabling.
               2.14.3.2  Power Supply Cabling for Digital Equipment Generally


                         Provide tray linking between the location of the IT Power distribution board and the final
                         terminal points  for the installation on power supply cabling associated with the digital
                         equipment.
                         Tray will be medium duty the width of tray will vary between 200mm and 50mm, the
                         selected width will be sufficient to allow the installation of all power cabling.

               2.14.3.3  Counter

                         The counter is supplied complete with two lines of dado trunking fixed to the back of the
                         facia panel. The Electrical Contractor will provide links between the ceiling level
                         containment and the counter trunking as follows:

                          •  2 x 25mm conduit for power
                          •  2 x 50mm ducts for data

               2.14.3.4  Digital Tablet Tables


                         The digital tablet table is supplied complete with internal wire ways and socket outlets for
                         the connection of the digital equipment.
                         The Electrical Contractor will provide containment linking between  the ceiling level
                         containment or floor chase and the tablet table as follows:

                          •  2 x 25mm conduit for power
                          •  2 x 50mm ducts for data

               2.14.3.5  Presenter and Order Take Booths


                         Provide three compartment dado trunking for the installation  power sockets and data
                         cabling. The dado trunking is to be routed down from the ceiling and around the
                         perimeter of the booth.





                                                      McDonalds Restaurants Ltd

                                                                58