GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         Screens and digital equipment generally will be provided by the McDonalds specialist
                         Contractor.

               2.14.1  Power Supplies

               2.14.1.1  IT Power Distribution


                         Provide a dedicated distribution board for the connection of all data equipment supplies
                         to be located in the Managers office, reference IP.
                         The distribution pan assembly will be single phase with a minimum of 12 ways. The final
                         number of circuit ways will be determined by the Electrical Contractor according to the
                         quantity and distribution of digital equipment to be installed and allowing for 4 spare
                         ways.

                         The distribution board will comply with the requirements for sub-main distribution boards
                         described elsewhere in this specification.

                         All circuits will be complete with 30mA RCD protection.

               2.14.1.2  Digital Equipment Cabinet

                         Provide two discrete circuits for the connection of the central equipment cabinet in the
                         manager’s office, unless otherwise indicated by the Architects drawings.

                         The circuits will be terminated in 16A, SP&N, in-line CeeForm sockets located above the
                         ceiling in the Managers office.

               2.14.1.3  Display Screens Generally

                         Provide a switched twin socket located in the ceiling void fixed immediately above the
                         location of the screen identified on the Architects drawing.

               2.14.1.4  Digiplay

                         Provide a switched twin socket located in the ceiling void fixed immediately above the
                         location of the digiplay projector as identified on the Architects drawing.

               2.14.1.5  Self-Order Kiosks (SOK)

                         Provide a switched twin socket adjacent to the location of the SOK as identified on the
                         Architects drawing. The SOKs will be fed from a dedicated radial circuit; the circuit to the
                         SOK will not be connected to any other devices or equipment.

                         The final location of the socket will be determined by the containment route to the kiosk,
                         i.e. whether it is connected to the ceiling or floor only.
                         For kiosks with a ceiling connection the socket will be located in the ceiling void directly
                         above the kiosk.