Page 79 - RotF - Electrical Specification_Neat
P. 79

GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



               2.14.1.9  Crew Room


                         Provide a twin switched socket at each PC desk position, at the location indicated on the
                         Architects drawings.
               2.14.1.10 Managers Office


                         Provide services as follows:
                         Position Type               Service Requirements
                         Desk                        3 x twin sockets for  each seating
                                                     position
                                                     Data & telephone outlets
               2.14.1.11 Order Take Booth (Booth 1)


                         Provide services as follows:
                         Position Type               Service Requirements
                         For each desk position      1 x twin socket
                                                     1 x fused connection unit
                                                     Data & telephone outlets


               2.14.1.12 Presenter Booth (Booth 2)

                         Provide services as follows:

                         Position Type               Service Requirements
                         Desk                        2 x twin sockets
                                                     Data & telephone outlets


               2.14.2  Socket Outlets and Connection Units for Data Services

                         BS1363 switched socket outlets shall be as manufactured by MK Electric, their catalogue
                         reference K2746D1RED.

                         16A sockets for the connection of the IT cabinet in the manager office or stock room shall
                         be as manufacture by Menneke Electrical Ltd., their PowerTOP range, model number 510
                         with corresponding plug 248.

                         Sockets will be labelled with circuit number and distribution board reference.

                         It shall be noted that all socket outlets must be protected by an earth leakage protection
                         device within the main L.V. distribution equipment rated at 30mA.