Page 14 - McD_ROTF DRAINAGE & PIPED SERVICES_Neat
P. 14

Drainage & Piped Services Standard Specification
Version 2014-1

                1. All testing and commissioning as prescribed elsewhere is complete to the
                     satisfaction of the PM and record of tests has been provided by the Contractor.
                     These are to form part of the maintenance manual to be supplied.

                2. Spares, tools, equipment etc have been passed to the Client.
                3. Operation and Maintenance manuals, instruction charts, diagrams, record

                     drawings etc. have been submitted, approved and supplied.
                4. A complete demonstration of every service has been carried out with full

                     functional operational controls tested and demonstrated and instructions given
                     to Client's staff to show proper working.

1.2.16 British Standard Specifications

             All equipment, materials and workmanship are to comply fully with the requirements
             of the relevant British Standard and/or its European equivalent (BS EN ISO)

1.2.17 Specialist Trade Attendance on Plant and Equipment

             The Contractor is to arrange and make payment for specialist tradesmen to visit site,
             adjust and put into working order all items of specialised plant and equipment supplied
             under the Contract.

1.2.18 Cleaning Down Equipment

             On completion of the works or section of the works any new item and/or existing item
             of equipment that has been soiled (by the Contractor or his Sub-Contractors) are to be
             thoroughly cleaned internally and externally and where applicable polished by the
             Contractor.

1.2.19 Maintenance of New Equipment

             All items of equipment whether put into operation before the completion of the
             Contract or not must be maintained in perfect order by the Contractor until the
             Practical Completion of the installation or until an agreed section of the installation is
             officially handed over to the Client.

1.2.20 Discrepancies

             Any apparent discrepancies within the Employers Requirements are to be noted at the
             time of tendering. No claim for extra costs shall be considered in respect of any item
             described in the Employers Requirements.

1.2.21 Testing and Commissioning Of the Works

             The Contractor is to undertake a pre commissioning exercise of the installations to
             prove correct operation of lighting control and other interlocked systems, air and water
             flow rates and temperatures and water condition.

             The Contractor is to carry out all necessary commissioning and testing, both as the
             installation proceeds and on completion to ensure the correctness of the installation
             and its compliance with the following (where no suitable code exists for commissioning
             an item of plant, the manufacturer's recommended method of commissioning should
             be used). The Contractor shall be required to re commission the entire system
             installations where all or part of the systems has been effected/altered by the works
             required by these employers’ requirements: