2/DESCRIPTION


              2.4 Specifications

              Specifications                         Indicating Gauge                  Switch Gauge
              Indicated Range
              Nominal 50 psi Medical
              Gases (Oxygen, Air,                    0-100 psi                         0-100 psi
              Nitrous Oxide, Carbon Dioxide)
              Nominal 180 psi Nitrogen               0-300 psi                         0-300 psi
              Vacuum Systems                         0-30 in. Hg.                      0-30 in. Hg.
              Accuracy
              Nominal 50 psi Medical                 ± 2 psi (25-75 psi)               ± 2 psi (33-66 psi)
              Gas                                    ± 3 psi elsewhere                 ± 3 psi elsewhere
              Nominal 180 psi                        ± 6 psi (75-225 psi)              ± 6 psi (100-200 psi)
              Nitrogen                               ± 9 psi elsewhere                 ± 9 psi elsewhere
              Vacuum Systems                         ± .6 in. Hg. (7.5-22.5 in. Hg.)   ± .6 in. Hg. (10-20 in. Hg.)
                                                     ± .9 in. Hg. elsewhere            ± .9 in. Hg. elsewhere
              Overpressure Limit
              Nominal 50 psi Medical Gas             110 psig                          150 psi
              Nominal 180 psi Nitrogen               330 psig                          400 psi
              Vacuum Systems                         0                                 45 psi

              Adjustable Range
              Nominal 50 psi Medical Gas             N.A.                              40-80 psi
              Nominal 180 psi Nitrogen               N.A.                              125-225 psi
              Vacuum Systems                         N.A.                              10-20 in. Hg.

              Switch Gauge                           Factory Set Points
              Oxygen, Nitrous Oxide,                 40 psig (decr. pres.) &
              Air, Carbon Dioxide                    60 psig (incr. pres.)
              (50 psi line pressure)
              Nitrogen                               160 psig (decr. pres.) &
              (180 psi line pressure)                200 psig (incr. pres.)
              Vacuum Systems                         12 in. Hg. (decr. vac.)
              (19-25 in. Hg. line vac.)


              2.4.1 Electrical Characteristics                  Alarm Indicators:  Visual- Light emitting diode bars (Red
                                                                LED) Audible- Horn 90 db at 2200 Hz
              Power Requirements:  120 VAC (operating range 104
              127), 60 Hz from emergency supply, 25 watts max. 220  Remote Alarm:  Relay Contacts- 250 mA at
              VAC (operating range 198-242), 50 Hz from emergency
                                                                28VDC/30VAC
              supply, 25 watts max-Export Only
                                                                Normal Indicators:  Visual- Light emitting diode
              Transformer: 120 VAC primary/14.0 vac secondary; 40  (Green LED)
              VA. 220 VAC primary/14.0 vac secondary: 40 VA-Export
              Only                                              Leakage Current: Less than 100 ,uA (with ground open)

              Note:  The 120 VAC Model is listed by Underwriters  Circuit Type:  Closed loop, alarm on ground contact or
              Laboratories. The 220 VAC unit has not been investigated.  open circuit.

              Circuitry:  Interconnecting wiring via locking connectors.  Control Unit:
              Microprocessor based; removable P.C. boards. 12VDC  Microprocessor:  Motorola 6805 Series
              and 5VDC operating voltages.