GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



                         Upon completion of the installation, the Electrical Contractor shall test and commission
                         the emergency lighting system to the requirements of BS 5266 : Part 1.

                         A test certificate similar to that detailed in  Appendix ‘A’ of BS 5266 : Part 1 shall be
                         completed and signed by the Electrical Contractor.

                         The original certificate shall be handed to the Project Manager and a copy shall be
                         included in the Operating and Maintenance Manual.
               2.12  GENERAL SMALL POWER


               2.12.1  Mixed Wiring Systems

                         Where mixed wiring systems exist, as in an existing building  under  refurbishment, the
                         Electrical Contractor should install a warning label at the interface between the old and
                         the new cabling.

                         This label should be yellow with a block type face with the following narrative.




                                                          CAUTION


                                                This installation has wiring colours


                                                  to two versions of BS 7671.









                         All new wiring shall use the new harmonised cable colours as indicated in Amendment No
                         2 (AMD 14905) to BS 7671: 2001.

               2.12.2  BS 1363 Socket Outlets

                         It shall be noted that all socket outlets must be protected by an earth leakage protection
                         device within the main L.V. distribution equipment rated at 30mA.
                         The  Electrical Contractor shall supply and install general  BS 1363  13A switched socket
                         outlets in the positions indicated on the Architects drawings.

                                                                           2
                         Cabling to sockets shall generally be installed as 4.0mm , 3-core YY cable.
                         Switched socket outlets shall be of the following types;





                                                      McDonalds Restaurants Ltd

                                                                48