GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



               2.12.2.1  Flush installations

                         Area                    Manufacture  Reference Number

                         Kitchen                   MK twin     MK Masterseal 56482GRY
                         Drive thu booths          MK twin     MK Ref K2747 WHI
                         Crew room training        MK twin     MK Ref K2747 WHI
                         Manager                   MK twin     MK Ref K2747 WHI
                         Restaurant lobby          MK twin     MK Ref K2948 MCO (or as specified by Interior
                                                               Designer)
                         Public toilets            MK FCU      MK Ref K941 MCO (or as specified by the
                                                               interior designer)
                         Wash up                   MK twin     MK Masterseal 56482GRY

               2.12.2.2  Surface installations


                         Area                    Manufacture  Reference Number
                         Store Multiplex           MK twin     MK Masterseal 56482GRY
                         Plantroom Switchroom      MK twin     MK Masterseal 56482GRY

               2.12.2.3  Mounting Heights


                         The mounting height of socket outlet shall generally comply with the requirements of Part
                         M of the building regulations; as the following table unless otherwise indicated by the
                         Architects drawings:
                          Thermostats                  1650mm to centre
                          Fire alarm break-glass unit   1200mm to centre
                          BS1363 socket outlets for 450mm to bottom  (or 150mm above worktop level to
                          internal installations       centre).
                          BS1363 and BS EN 60309 1200mm to centre
                          socket outlets for external
                          installations

                          BS EN 60309 sockets for Refer to specific equipment requirements identified by
                          kitchen areas                H&K.
                          FCUs in public spaces        2200mm above finished floor

                         Flush socket outlets shall be mounted on steel boxes to BS 4662 : 1989. Surface mounted
                         socket outlets shall be fitted to steel boxes to BS 5733 : 1995. All socket outlet boxes shall
                                                                     2
                         be fitted with a brass earth terminal. A 2.5mm  green/yellow insulated copper fly lead
                         shall be fitted between the box and the socket outlet earth terminal.




                                                      McDonalds Restaurants Ltd

                                                                49