Finish Installation



            Building Automation System Wiring


             There are several methods of connecting           When alarm condition is corrected, relay
             MEGA2 alarm panels to a building                  contacts will close. Relay contact ratings
             automation system depending upon what             are 2 A @ 30 VDC/0.5 A @ 125 VAC.
             type of information is required and what          Refer to Figure Schematic 7 (Pg. 19).
             type of building automation system is
                                                               Annunciator Module General Fault Relay:
             being used.
                                                               The annunciator module is supplied with
             Multi-Signal Module Relays:                       an alarm panel general fault output relay.
             As an option, mutli-signal modules may            This relay has a set of dry contacts that
             be ordered with five output relays, one for       may be wired either normally open or
             each of five signals that multi-signal is         normally closed.  The relay will activate
             capable of monitoring.  Each relay has a          when ANY alarm on ENTIRE alarm panel
             set of dry, normally-closed contacts that         is activated.  Relay  will remain activated
             will open when an alarm is activated on           as long as alarm condition is active, even
             corresponding front panel signal.  For            if audible alarm is silenced by MUTE
             example, when an alarm condition                  button.  When alarm condition is
             activates on top multi-signal front panel         corrected, relay will deactivate. Relay
             alarm location (Signal 1), relay labeled
                                                               contact ratings are 2 A @ 30 VDC/0.5 A @
             “Signal 1” will activate opening its              125 VAC.  Refer to Schematic 6 (Pg. 19).
             contacts.  Relay contacts will remain open
             as long as alarm condition is active, even        Annunciator Module Auxiliary Relay:
                                                               As an option, annunciator module may be
             if audible alarm is silenced by MUTE
                                                               supplied with an additional auxiliary relay.
             button.  When alarm condition is
                                                               This auxiliary relay does not replace
             corrected, relay contacts will close. Relay
                                                               general fault relay described above.
             contact ratings are 2 A @ 30 VDC/0.5 A @
                                                               Auxiliary relay has a set of dry contacts
             125 VAC.  Refer to Schematic 5 (Pg. 18).
                                                               that may be wired either normally open or
             Digital Display Module High/Low                   normally closed.  Like general fault relay,
             Relays:                                           auxiliary relay will activate when ANY
             Each digital display module is supplied           alarm on ENTIRE alarm panel is initiated.
             with two separate output relays.  One             Unlike general fault relay, auxiliary relay
             relay for high line pressure alarm and            will deactivate when audible alarm is
             another for low line pressure alarm.
                                                               silenced by MUTE        button.  If alarm
             Each relay has a set of dry, normally-            condition is still active when mute function
             closed contacts that will open when an
                                                               cancels, auxiliary relay will reactivate.
             alarm is activated on corresponding front         Relay contact ratings are 2 A @ 30
             panel signal.  For example, when a low            VDC/0.5 A @ 125 VAC.  Refer to
             pressure alarm condition activates on
                                                               Schematic 6 (Pg. 19).
             digital display module front panel, relay
             labeled “Low Relay” will activate, opening
             its contacts.  Relay contacts will remain
             open as long as alarm condition is active,
             even if audible alarm is silenced by MUTE

                button.