Finish Installation



                Building Automation System Wiring                   Slave Panel Wiring


                Johnson Controls METASYS® System:                  Digital display modules of two alarm
                The MEGA2 alarm panel is compatible                panels may be wired together in such a
                with  Johnson Controls METASYS®                    way that pressure readings of first panel
                building automation system (Using                  can be duplicated at second panel.  Each
                METASYS® Integrator).  Each MEGA2                  digital display module has RS-422 digital
                alarm panel is connected to a common               outputs and inputs.  By connecting digital
                two-wire RS-485 serial computer interface          output (master output) of first panel to
                bus.  Two wires are connected to pins 1            digital inputs (slave input) of the second
                and 2 of annunciator module and then               panel, second panel will duplicate
                connected to common data bus.  Refer to            pressure readings.  Refer to Schematic 4
                Schematic 9 (Pg. 21) for details.  Each            (Pg. 17) for details.
                digital display module and multi-signal
                module within alarm panel is field
                programmed with a unique network
                address.  Using this address, Johnson
                Controls system can monitor alarm panel
                status including digital pressure readings
                and programmed alarm set points.